Home > Capacitor, Fuse, Circuit Breaker > FSC 5925 > 5925-00-027-6353

5925-00-027-6353, 5925000276353 NSN Information

Request for Quote

Manufacturer Part Number(s):271-1290P26, 70-613A4MG6-6-115VAC-4, S271-1290P26

FSC NIIN ITEM NAME
5925 000276353 CIRCUIT BREAKER
INC ESDC HMIC
0013 P

5925-00-027-6353 MCRD (Master Cross Reference Data)

Mfg. Part # Mfg. Name CAGE RNCC RNVC ISC MSDS SADC DAC HCC
271-1290P26 RAYTHEON COMPANY 49956 5 9 C
271-1290P26 RAYTHEON TECHNICAL SERVICES COMPANY 3B150 3 2 C
70-613A4MG6-6-115VAC-4 EATON CORP 74193 5 9 C
S271-1290P26 EATON CORP 74193 5 9 C
S271-1290P26 U S DEPT OF TRANSPORTATION 08125 3 2 C

5925-00-027-6353 Characteristics

MRC Requirement Statement Characteristics
CPSM INTERNAL TRIP RELEASE CONFIGURATION SERIES TRIP SINGLE LOCATION
AXHR MOUNTING FACILITY TYPE AND QUANTITY 2 THREADED HOLE
CPRH CIRCUIT PROTECTION TYPE OVERCURRENT SINGLE LOCATION
CPRL TRIP RELEASE CHARACTERISTIC TIME DELAY SINGLE LOCATION
ADAT BODY WIDTH 0.740 INCHES MINIMUM AND 0.760 INCHES MAXIMUM
ADAQ BODY LENGTH 2.490 INCHES MINIMUM AND 2.510 INCHES MAXIMUM
APNQ III ARC QUENCHING METHOD MAGNETIC BLOWOUT
CPRW ACTUATOR FUNCTION TRIP-RESET
CPRT MANUAL ACTUATOR TYPE AND QUANTITY 1 TOGGLE
CPRN ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT 125.0 SINGLE LOCATION
CPRQ RESET METHOD MANUAL
TTQY TERMINAL TYPE AND QUANTITY 2 THREADED STUD
FREQ FREQUENCY IN HERTZ 60.0 SINGLE LOCATION
CPRJ TRIP RELEASE METHOD MAGNETIC-HYDRAULIC SINGLE LOCATION
CPLM MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE 6.0 AMPERES AC SINGLE LOCATION
AJWX MOUNTING SURFACE TO TERMINAL END DISTANCE 2.451 INCHES MINIMUM AND 2.471 INCHES MAXIMUM
CQXF INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED DUSTPROOF
AFJN III FRAGILITY FACTOR MODERATELY RUGGED
AAQL BODY STYLE SINGLE POLE TYPE
CQWN TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT 4.000 MINIMUM AT 200 PCT AND 10.000 MAXIMUM AT 200 PCT SINGLE LOCATION
CPRF OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS 115.0 AC SINGLE LOCATION
THSD THREAD SERIES DESIGNATOR UNC
CPRG MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS 1000.0 AC SINGLE LOCATION
ADTV CASE MATERIAL PLASTIC
CPRR MAIN CONTACT TRIPPING MECHANISM TYPE TRIP FREE
AJEC BOSS HEIGHT 0.130 INCHES MINIMUM AND 0.150 INCHES MAXIMUM
AEBY DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH 2.050 INCHES MINIMUM AND 2.070 INCHES MAXIMUM
CMLP THREAD QUANTITY PER INCH 32
BBRG III STORAGE TYPE GENERAL PURPOSE WAREHOUSE
CQJX NOMINAL THREAD SIZE 0.138 INCHES
AKPX POLE QUANTITY 1
AEBP CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH 1.928 INCHES MINIMUM AND 1.948 INCHES MAXIMUM
AGAV III END ITEM IDENTIFICATION AIR ROUTE SURVEILLANCE RADAR 1, ARSR1
CPRX ACTUATOR POSITION DESIGNATION AT POLE ONE