Home > Capacitor, Fuse, Circuit Breaker > FSC 5925 > 5925-00-902-1883

5925-00-902-1883, 5925009021883 NSN Information

Request for Quote

Manufacturer Part Number(s):165040-1, AP112-1-4-1-123, SM333-12-115VAC400C58

FSC NIIN ITEM NAME
5925 009021883 CIRCUIT BREAKER
INC ESDC HMIC
0013 P

5925-00-902-1883 MCRD (Master Cross Reference Data)

Mfg. Part # Mfg. Name CAGE RNCC RNVC ISC MSDS SADC DAC HCC
165040-1 RAYTHEON COMPANY 37695 5 2 5
AP112-1-4-1-123 SENSATA TECHNOLOGIES MARYLAND INC 81541 5 2 5
SM333-12-115VAC400C58 EATON CORP 74193 3 9 5

5925-00-902-1883 Characteristics

MRC Requirement Statement Characteristics
CQJX NOMINAL THREAD SIZE 0.375 INCHES
AJWX MOUNTING SURFACE TO TERMINAL END DISTANCE 1.678 INCHES NOMINAL
AAQL BODY STYLE MULTIPOLE-SINGLE ACTUATOR TYPE
CPRF OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS 115.0 AC ALL LOCATIONS
CPLM MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE 12.0 AMPERES AC ALL LOCATIONS
ADTV CASE MATERIAL METAL
APNQ III ARC QUENCHING METHOD MAGNETIC BLOWOUT
CPRW ACTUATOR FUNCTION TRIP-RESET
CPRX ACTUATOR POSITION DESIGNATION AT POLE TWO
CPRT MANUAL ACTUATOR TYPE AND QUANTITY 1 TOGGLE
THSD THREAD SERIES DESIGNATOR UNEF
ADAQ BODY LENGTH 1.495 INCHES NOMINAL
CPRL TRIP RELEASE CHARACTERISTIC TIME DELAY ALL LOCATIONS
CPRQ RESET METHOD MANUAL
AXHR MOUNTING FACILITY TYPE AND QUANTITY 1 THREADED BUSHING W/PANEL SEAL
AAJE THREAD PITCH DIAMETERS 0.3503 TO 0.3537 INCHES
CPRN ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT 150.0 ALL LOCATIONS
BBRJ III SPECIAL HANDLING FEATURE MAGNETIC
CPRJ TRIP RELEASE METHOD MAGNETIC-HYDRAULIC ALL LOCATIONS
AFJN III FRAGILITY FACTOR MODERATELY RUGGED
FREQ FREQUENCY IN HERTZ 400.0 ALL LOCATIONS
AEBQ CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH 0.625 INCHES NOMINAL
CPRG MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS 500.0 AC ALL LOCATIONS
CPRR MAIN CONTACT TRIPPING MECHANISM TYPE TRIP FREE
CMLP THREAD QUANTITY PER INCH 32
BBRG III STORAGE TYPE GENERAL PURPOSE WAREHOUSE
ADAT BODY WIDTH 1.872 INCHES NOMINAL
TTQY TERMINAL TYPE AND QUANTITY 6 WIRE HOOK
CQXF INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED HERMETICALLY SEALED
CQWN TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT 0.160 MINIMUM AT 200 PCT AND 0.600 MAXIMUM AT 200 PCT ALL LOCATIONS
AEBP CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH 0.875 INCHES NOMINAL
AKPX POLE QUANTITY 3
CPSM INTERNAL TRIP RELEASE CONFIGURATION SERIES TRIP ALL LOCATIONS
CPRH CIRCUIT PROTECTION TYPE OVERCURRENT ALL LOCATIONS
ABXD BUSHING LENGTH 0.375 INCHES NOMINAL