| MRC |
Requirement Statement |
Characteristics |
| CPRJ |
TRIP RELEASE METHOD |
MAGNETIC ALL LOCATIONS |
| AAQL |
BODY STYLE |
MULTIPOLE-MULTIPLE ACTUATOR TYPE |
| AEBY |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH |
2.052 INCHES MINIMUM AND 2.072 INCHES MAXIMUM |
| AXHR |
MOUNTING FACILITY TYPE AND QUANTITY |
8 THREADED HOLE |
| AEGJ |
SWITCH CONTACT ARRANGEMENT |
SINGLE POLE, DOUBLE THROW |
| TTQY |
TERMINAL TYPE AND QUANTITY |
10 THREADED STUD |
| ADAQ |
BODY LENGTH |
2.490 INCHES MINIMUM AND 2.510 INCHES MAXIMUM |
| APNQ |
III ARC QUENCHING METHOD |
MAGNETIC BLOWOUT |
| CPRW |
ACTUATOR FUNCTION |
TRIP-RESET |
| CQWN |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT |
2.200 MINIMUM AT 200 PCT AND 20.000 MAXIMUM AT 200 PCT FIRST LOCATION 2.200 MINIMUM AT 200 PCT AND 20.000 MAXIMUM AT 200 PCT SECOND LOCATION 2.200 MINIMUM AT 200 PCT AND 20.000 MAXIMUM AT 200 PCT THIRD LOCATION |
| CRTK |
SWITCH TERMINAL TYPE |
TAB, SOLDER LUG |
| CPRF |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS |
250.0 AC ALL LOCATIONS |
| CPRQ |
RESET METHOD |
MANUAL |
| CPRY |
EXTERNAL ACTUATOR LINKAGE ARRANGEMENT |
ONE, TWO, THREE, AND FOUR LINKED |
| FREQ |
FREQUENCY IN HERTZ |
50.0 OR 60.0 OR 400.0 ALL LOCATIONS |
| AFJN |
III FRAGILITY FACTOR |
MODERATELY RUGGED |
| CQXF |
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED |
FUNGUS RESISTANT AND VIBRATION RESISTANT |
| AEBQ |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH |
0.740 INCHES MINIMUM AND 0.760 INCHES MAXIMUM |
| CPRZ |
AUXILIARY SWITCH FUNCTION AND QUANTITY |
1 ALARM |
| CPSM |
INTERNAL TRIP RELEASE CONFIGURATION |
SERIES TRIP FIRST LOCATION SERIES TRIP SECOND LOCATION SERIES TRIP THIRD LOCATION RELAY TRIP FOURTH LOCATION |
| THSD |
THREAD SERIES DESIGNATOR |
UNC |
| CPLM |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE |
60.0 AMPERES AC ALL LOCATIONS |
| ADTV |
CASE MATERIAL |
PLASTIC |
| CPRR |
MAIN CONTACT TRIPPING MECHANISM TYPE |
TRIP FREE |
| AJEC |
BOSS HEIGHT |
0.130 INCHES MINIMUM AND 0.150 INCHES MAXIMUM |
| CPRG |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS |
1000.0 AC ALL LOCATIONS |
| CPRT |
MANUAL ACTUATOR TYPE AND QUANTITY |
4 TOGGLE |
| CMLP |
THREAD QUANTITY PER INCH |
32 |
| BBRG |
III STORAGE TYPE |
GENERAL PURPOSE WAREHOUSE |
| CQJX |
NOMINAL THREAD SIZE |
0.138 INCHES |
| CPRN |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT |
115.0 ALL LOCATIONS |
| CPRL |
TRIP RELEASE CHARACTERISTIC |
TIME DELAY FIRST LOCATION TIME DELAY SECOND LOCATION TIME DELAY THIRD LOCATION INSTANTANEOUS FOURTH LOCATION |
| CSSX |
SWITCH CURRENT RATING AND TYPE IN AMPS |
10.0 AC |
| AEBP |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH |
1.928 INCHES MINIMUM AND 1.948 INCHES MAXIMUM |
| CPRH |
CIRCUIT PROTECTION TYPE |
OVERCURRENT ALL LOCATIONS |
| CSWP |
SWITCH VOLTAGE RATING AND TYPE IN VOLTS |
125.0 AC |
| AJWX |
MOUNTING SURFACE TO TERMINAL END DISTANCE |
2.461 INCHES MINIMUM AND 2.481 INCHES MAXIMUM |
| ADAT |
BODY WIDTH |
2.990 INCHES MINIMUM AND 3.010 INCHES MAXIMUM |
| AEHA |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH |
0.740 INCHES MINIMUM AND 0.760 INCHES MAXIMUM |
| AKPX |
POLE QUANTITY |
4 |
| CPRX |
ACTUATOR POSITION DESIGNATION |
AT EACH POLE |
| AAJE |
THREAD PITCH DIAMETERS |
0.1177 TO 0.1214 INCHES |
| CQSM |
SWITCH LOCATION AND POSITION DESIGNATION |
INTERNAL AT POLE ONE |