Home > Capacitor, Fuse, Circuit Breaker > FSC 5925 > 5925-00-163-2070

5925-00-163-2070, 5925001632070 NSN Information

Request for Quote

Manufacturer Part Number(s):2519113-3, CH350-50AMP

FSC NIIN ITEM NAME
5925 001632070 CIRCUIT BREAKER
INC ESDC HMIC
0013 P

5925-00-163-2070 MCRD (Master Cross Reference Data)

Mfg. Part # Mfg. Name CAGE RNCC RNVC ISC MSDS SADC DAC HCC
2519113-3 NAVAL AIR SYSTEMS COMMAND 30003 1 2 2
CH350-50AMP EATON CORP 55841 3 2 2

5925-00-163-2070 Characteristics

MRC Requirement Statement Characteristics
CPRL TRIP RELEASE CHARACTERISTIC INSTANTANEOUS ALL LOCATIONS
AAQL BODY STYLE MULTIPOLE-MULTIPLE ACTUATOR TYPE
CQXF INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED GENERAL PURPOSE
SR-1 MFR SOURCE CONTROLLING REFERENCE 2519113-3
AXHR MOUNTING FACILITY TYPE AND QUANTITY 6 TERMINAL
CRCF TRIP RELEASE AMBIENT TEMP RATING 40.0 DEG CELSIUS NOMINAL ALL LOCATIONS
ZZZK SPECIFICATION/STANDARD DATA 81348-W-C-375/07-008 GOVERNMENT SPECIFICATION
SR-1 SPEC/STD CONTROLLING DATA
CPRY EXTERNAL ACTUATOR LINKAGE ARRANGEMENT ONE, TWO, AND THREE LINKED
CPRW ACTUATOR FUNCTION TRIP-RESET
CPRF OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS 240.0 AC ALL LOCATIONS
CPLM MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE 50.0 AMPERES AC ALL LOCATIONS
AJEC BOSS HEIGHT 0.188 INCHES NOMINAL
ADAQ BODY LENGTH 3.025 INCHES MINIMUM AND 3.065 INCHES MAXIMUM
CPRQ RESET METHOD MANUAL
TTQY TERMINAL TYPE AND QUANTITY 6 CLIP
CPRG MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS 10000.0 AC ALL LOCATIONS
BBRJ III SPECIAL HANDLING FEATURE MAGNETIC
AFJN III FRAGILITY FACTOR MODERATELY RUGGED
SR-1 MANUFACTURERS CODE 30003
AEBQ CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH 0.424 INCHES NOMINAL
CPRN ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT 125.0 ALL LOCATIONS
ADTV CASE MATERIAL PLASTIC
CPRR MAIN CONTACT TRIPPING MECHANISM TYPE TRIP FREE
FREQ FREQUENCY IN HERTZ 60.0 ALL LOCATIONS
CPRT MANUAL ACTUATOR TYPE AND QUANTITY 3 TOGGLE
ADAT BODY WIDTH 2.193 INCHES MINIMUM AND 2.241 INCHES MAXIMUM
BBRG III STORAGE TYPE GENERAL PURPOSE WAREHOUSE
ADAU BODY HEIGHT 2.371 INCHES MINIMUM AND 2.433 INCHES MAXIMUM
AKPX POLE QUANTITY 3
CPRH CIRCUIT PROTECTION TYPE OVERCURRENT ALL LOCATIONS
CPRJ TRIP RELEASE METHOD THERMAL-MAGNETIC ALL LOCATIONS
CPRX ACTUATOR POSITION DESIGNATION AT EACH POLE